El presente proyecto es un estudio de las causas que produjeron el incendió, ocurrido el 23 de Junio de 2017 de la Central Hidráulica (CH) Las Playas, localizada en Antioquia, Colombia. Esta central consta de tres grupos generadores (cada uno con una potencia de
69 MW, y por tanto una capacidad total de 207 MW), con su respectivo transformador de potencia cada uno. Dicho incendio se produjo por una explosión en el domo de la fase T del transformador de potencia número 3, propagándose hacia los otros dos transformadores y en definitiva a la totalidad de la central.

El objetivo era analizar todas las pruebas e informes para llegar a la causa raíz del incidente. Se comenzó analizando un informe realizado por EPM, quienes concluyeron que el incendio fue producido por una fisura en una pieza que participaba en el aislamiento y conexión del terminal interior del transformador. Finalmente, tras seguir investigando se concluyo que la causa raíz estaba relacionada con el diseño de la conexión. Este incidente supuso una perdida de casi 21 millones de euros y solo teniendo en cuenta la energía que se pudo producir si la centrar hubiera estado operativa durante su reconstrucción.

Idioma en-GB
Resumen

This project is a study of the causes of the fire that occurred on 23 June 2017 at the Las Playas Hydraulic Power Station (CH), located in Antioquia, Colombia. This plant consists of three generator groups (each with a power of 69 MW, and therefore a total capacity of 207 MW), with their respective power transformer each. This fire was caused by an explosion in the dome of phase T of power transformer number 3, which spread to the other two transformers and ultimately to the entire plant.

The objective was to analyse all the tests and reports in order to arrive at the root cause of the incident. We started by analysing a report made by EPM, who concluded that the fire was caused by a crack in a piece that was involved in the insulation and connection of the transformer's inner terminal. Finally, after further investigation it was concluded that the root cause was related to the design of the connection. This incident meant a loss of almost 21 million euros and only taking into account the energy that could have been produced if the centre had been operative during its reconstruction.

Centro
Escuela Técnica Superior de Ingeniería (ICAI)

Palabras clave

Tipo de archivo application/pdf
Idioma en-GB
Tipo de acceso info:eu-repo/semantics/closedAccess
Licencia http://creativecommons.org/licenses/by-nc-nd/3.0/us/
Fecha de modificacion 09/09/2022
Fecha de disponibilidad 17/06/2019
fecha de alta 17/06/2019

Categorías:

Compartida con: